transformers insulation varnished cloth Alkyd varnished glass cloth
- Delivery Time:
- 5 Days
Quantity:
Your message must be between 20 to 2000 characters
Contact NowBasic Info
Basic Info
Place of Origin: | Henan, China (Mainland) |
---|
Product Description
Product Description
Specifications insulation varnished cloth Alkyd varnished glass cloth
1. passed UL ROHS
2. as coil insulation for oil-immersed transformer

insulation varnished cloth Alkyd varnished glass cloth Basic Material: E-glass fiber cloth
Impregnated Varnish: Alkyd resin
Temp. class: B(130) insulation varnished cloth Alkyd varnished glass cloth's Features and Applications:
- Alkyd varnished glass cloth has excellent dielectric, mechanical property and heat resistance, good oil, fungus and humidity-heat resistance
- Alkyd varnished glass cloth can be used as coil insulation for oil-immersed transformers and oil circuit breakers.
insulation varnished cloth Alkyd varnished glass cloth's Availability:
-Thickness: 0.06mm-0.25mm
-Form: roll (width: 900-1500mm), strips (width: >10mm insulation varnished cloth Alkyd varnished glass cloth's technical data:
1. passed UL ROHS
2. as coil insulation for oil-immersed transformer



Impregnated Varnish: Alkyd resin
Temp. class: B(130) insulation varnished cloth Alkyd varnished glass cloth's Features and Applications:
- Alkyd varnished glass cloth has excellent dielectric, mechanical property and heat resistance, good oil, fungus and humidity-heat resistance
- Alkyd varnished glass cloth can be used as coil insulation for oil-immersed transformers and oil circuit breakers.
insulation varnished cloth Alkyd varnished glass cloth's Availability:
-Thickness: 0.06mm-0.25mm
-Form: roll (width: 900-1500mm), strips (width: >10mm insulation varnished cloth Alkyd varnished glass cloth's technical data:
Properties | Units | Values | ||||||||||
Nominal thickness | mm | 0.10 | 0.12 | 0.15 | 0.18 | 0.20 | ||||||
Oil resistance | / | Not lower than breakdown voltage at 23±2°C | ||||||||||
Humidity-heat resistance | / | Varnished film shall not be peeled off | ||||||||||
Flexibility resistance | / | Not break the medium value of breakdown voltage at bended place shall not be less 50% than that at unbended place | ||||||||||
Tensile strength | Length | N/10mm | ≥65 | ≥85 | ≥105 | ≥111 | ≥118 | |||||
Cross | ≥45 | ≥52 | ≥65 | ≥78 | ≥85 | |||||||
45° | ≥40 | ≥60 | ≥65 | ≥78 | ≥70 | |||||||
On lapping place cut on bias | Before impregnation | ≥20 | ≥25 | ≥30 | ≥30 | ≥30 | ||||||
After impregnation | ≥20 | ≥20 | ≥20 | ≥30 | ≥30 | |||||||
Breakdown voltage | Under 23±2°C | Medium | kV | ≥5.0 | ≥6.0 | ≥7.0 | ≥8.0 | ≥9.0 | ||||
Min | ≥4.0 | ≥4.5 | ≥6.0 | ≥6.5 | ≥7.0 | |||||||
Under 130±2°C | Medium | ≥2.5 | ≥3.0 | ≥3.5 | ≥4.0 | ≥4.5 | ||||||
The quality warranty period | Six months(under 25°C) |